Category:Dry Type Transformer
Phase: Three Phase
Primary Voltage Ratings: 35KV-38.5KV or Custom
Secondary Voltage Ratings: 200v-440v or Custom
Rated Capacity: 30-3000KVA or Custom
Rated Frequency: 50/60HZ

1. It is safe, fireproof, pollution-free, and can be directly operated in the load center;
2. Using domestic advanced technology, high mechanical strength, strong short-circuit resistance and good thermal stability
3. Low loss, low noise, obvious energy saving effect, maintenance-free;
4. Good heat dissipation performance, strong overload capacity, and capacity operation can be increased when forced air cooling;
5. Good moisture-proof performance, adapt to high humidity and other harsh environments;
6. Dry-type transformers can be equipped with a complete temperature detection and protection system.
7. Small size, light weight, less space and low installation cost.
| SCB 10(11)Series 35kV level resin insulation dry-type power transformers technical parameters | |||||||
| Rated Capacity KVA |
Voltage Combination | Vector group |
load Loss (120℃)(W) |
No-load power(W) | Impedance (%) |
||
| High Voltage (KV) |
Tapping Range (%) |
Low Voltage (KV) |
|||||
| 50 | 35-38.5 | ±2×2.5 ±5 | 0.4 | Dyn11 or Yyn0 |
1420 | 450 | 6 |
| 100 | 2090 | 630 | |||||
| 160 | 2810 | 790 | |||||
| 200 | 3320 | 880 | |||||
| 250 | 2880 | 990 | |||||
| 315 | 4510 | 1170 | |||||
| 400 | 5410 | 1370 | |||||
| 500 | 6650 | 1620 | |||||
| 630 | 7690 | 1860 | |||||
| 800 | 9120 | 2160 | |||||
| 1000 | 10400 | 2430 | |||||
| 1250 | 12700 | 2830 | |||||
| 1600 | 15400 | 3240 | |||||
| 2000 | 18200 | 3820 | |||||
| 2500 | 21800 | 4450 | |||||